PA-S1000
하드웨어
PA-S1000/4 | PA-S1000/8 | ||
---|---|---|---|
Number of analog channels | 4 | 8 | |
Analog input type | Voltage, platinum resistance temperature sensor (can be set by channel) | ||
Analog input method | Differential input, insulation between channels | ||
Input coupling | DC | ||
Input terminal shape | Screw type terminal block | ||
Input resistance (approx.) | 10 MΩ (for voltage input setting) | ||
Maximum non-destructive input voltage (analog input to GND) |
voltage | 150 V (DC + AC peak) | |
Pt100 | 50 V | ||
Insulation resistance (each analog terminal to digital GND) |
50 MΩ or more (at 500 VDC) | ||
Supported platinum resistance temperature sensors |
Pt100 (nominal 100 Ω) 3-wire type(measuring current: 1 mA) | ||
Platinum resistance temperature sensor resolution / temperature range |
0.1°C / -200°C to 800°C | ||
Measurement range | ±100 mV, ±200 mV, ±500 mV, ±1 V, ±2 V, ±5 V, ±10V, ±20 V, ±50 V and ±100 V | ||
Accuracy *1 (60 minutes or more after power activation) (23°C ± 5°C) |
voltage | ±100 mV range: ±1% of F.S./ ±200 mV range: ±0.5% of F.S. Other ranges: ±0.1% of F.S. | |
Platinum resistance temperature sensor |
±0.25% of rdg ±2.5°C (not including sensor accuracy) | ||
Sampling time(measuring period) | 1 μs to 1 s (simultaneous sampling of all channels) | ||
Sampling rate accuracy | ±100 ppm | ||
Frequency characteristics | DC to 200 kHz(-3 dB) | ||
A/D resolution | 16 bits | ||
Trigger hysteresis (approx.) | 1% of full scale (for voltage input), 0.5°C (for Pt100) | ||
PC interface | USB 2.0 (High Speed) self-powered | ||
Rated power supply | 100 to 240 VAC, 50 to 60 Hz (AC/DC adapter) | ||
Consumption current (approx.) | 1.8 A at 12 V | 3.5 A at 12 V | |
Operating environment | 0 to 40°C, 20 to 80% RH (non condensing) | ||
Dimensions (mm, approx.) | 151 (W) x 25 (H) x 210 (D) | ||
Weight (approx.) not including AC/DC adapter |
750 g | 960 g |
Digital Input/Output Part
Connector | D-Sub 25-pin Female |
Digital Input | TTL-level, non-isolated 8-channel Input filter for preventing chattering can be set: 1 to 127 ms |
Digital Input voltage | Low: 0.8V or less, High: 2.0 V or more |
Minimum pulse width for trigger detection | 50 ns |
Digital output | TTL-level, non-isolated 4-channel, open-collector |
Digital output voltage | Low: 0.2V or less(when drawing 100 mA), High: approx. 5 V (pulled up by internal 10kΩ |
General purpose relay | 2 pole (open to the connector on both coil and contact sides) |
General purpose relay specifications | Coil side: 5 V/21.1 mA, model number: OMRON G6k-2G-Y5V or equivalent |
Power output for external circuit | 5 V, 100 mA or less and 12 V, 100 mA or less |